FI-MDJD-01(EKL-3)

EKL--3Panel Mounted Short Circuit and Earth Fault Indicator

 Models and Specifications

FI-MDJD-01(EKL-3)

 Main Functions

1. Short Circuit Alarm Indication: If a short circuit fault occurs

 

in the power line and the current reaches or exceeds the threshold

of alarm current. Short-circuit sensor sends out a alarm signal

which will be transmitted to a host through optical fiber. And then

the host generates a corresponding alarm indication signal after receiving this signal.

2. Earth Fault Alarm Indication: If an earth fault occurs in the power line and current reaches or exceeds the

threshold of alarm current. An earth fault sensor sends out a alarm signal which will be transmitted to a host

through optical fiber. And then the host generates a corresponding alarm indication signal after receiving this

signal.

3. Automatic Reset: If indicator sends out a signal and there is no manual reset implemented or delay time

exceeds configured automatic reset time. Indicator will be reset automatically. The automatic reset time is 12 or

24 hours, or other time configured

4. Manual Reset/self-test: If alarm is activated, the indicator can be reset by triggering 'Test / Reset' button on

the control panel of the indicator to stop the alarm.It can also be self tested by pressing the 'Test / Reset' button

for 2 seconds.

5. Automation(optional): Indicator generates a corresponding alarm indication signal which can be output to a

remote-transmission device,including short circuit fault,earth fault and low voltage alarm indication signal,as

well as the alarm signal of remote terminal reset fault.

 Technical Parameters

1.Short Circuit Current Alarm: ≥ 150A.Variation ± 10%; Default Setting

is 800A. Short Circuit Delay is 60ms

2.Earth Fault Current Alarm: 3A-200A Variation ± 10%; Default Setting

is 10A. Short Circuit Delay is 40ms

3. Operating Power: ER14505 Lithium Battery 3. 6V

4. Standby Current of Unit: ≤ 5μA

5. Auto Reset Time: 12 or 24 hours, can be configured

according to the requirement.

6. Indicator Protection Level: Host IP40; Sensor IP65

7. Maximum Withstand Current of Short-circuit Current Sensor: 20KA/4S

8. Ambient Temperature: -40 ℃ - +65 ; Relative Humidity ≤ 95%; Waterproof, Anti-acid, Anti-salt Spray.

9. Host Mounting Dimension: Host Dimension: 96mm × 49mm × 85mm; Hole Dimension: Length 91mm ×Width 43mm.